← All Refrigerant PT Charts

R-134a Pressure Temperature Chart

Saturation pressure (PSIG) for R-134a at temperatures from -40°F to 120°F. The standard for automotive AC and medium-temp refrigeration.

Use the interactive PT chart with calculator →
Temp (°F)Pressure (PSIG)
-40°F-6.8 vac
-20°F2.4
0°F14.7
20°F30.1
40°F49.7
60°F74.3
80°F104.3
100°F140.7
120°F184.3

Frequently Asked Questions

What is the saturation pressure of R-134a at 75°F?

At 75°F, R-134a has a saturation pressure of approximately 96.8 PSIG (interpolated between 74.3 PSIG at 60°F and 104.3 PSIG at 80°F).

What is R-134a used for?

R-134a (1,1,1,2-tetrafluoroethane) is widely used in automotive air conditioning, medium-temperature commercial refrigeration, and chillers. It replaced R-12 in automotive applications.

At what temperature does R-134a go into vacuum?

R-134a drops below 0 PSIG (into vacuum) at temperatures below approximately -15°F. At -40°F, R-134a reads -6.8 PSIG (vacuum). This is important to note when diagnosing low-temperature systems.